Air break switch NX2001151

Air break switch NX2001151

Overhead switch IA2CM is installed at the end of the line in a structured MV three-phases 36 kV networks, enables a group of stations to be isolated, so that live line work can be carried out downstream

Code NX2001151
GTIN 03700540412642
Name Air break switch
IA2CM 36kV 400A 80A 25kA F2T0E2
Contact sales

Technical information

Technical specifications

Dimensions
Weight 148 kg
Height 660 mm
Width 1535 mm
Length 2000 mm
Standards
Standards IEC 60265, IEC 62271-103
Features
Electrical endurance 100 C/O
Mechnanical endurance 1000 C/O
Isolator type Ceramic
Option 1 - Threaded rods for clamping
Option 2 - Tiges filetées pour le serrage
Electrical values
Rated Voltage (Ur) 36 kV
Rated current 400 A
Rated short-circuit making current 25 kA
Rated short-time withstand current (1s) 10 kA/s
Rated short-time withstand current (peak) 25 kA/s
Rated mainly active load-breaking current 80 A
70 kV
Lightning impulse withstand level of voltage (1.2/50) 170 kV
Operating temperature -25 ... 40 °C
Storage temperature -25 ... 70 °C

Packaging

Pallet package
Size 1 pce
Weight 153.000 kg